⚡FreeFastCalculatorAll calculators

Wire Size Calculator (Amps to AWG)

Find the right wire gauge for 20, 30, 40, 50, 100 amp circuits. Uses NEC 310.16 ampacity, copper or aluminum, with voltage drop check and full amp chart.

Updated · Written and fact-checked by the FreeFast editorial team · Free, no sign-up

Derating: ambient temp & bundled wires
Voltage drop check (optional)
Minimum wire size10 AWG
Required ampacity30 A
This wire after derating30 A

Based on NEC 2023 Tables 310.16, 310.12(A), 310.15(B)(1)(1), 310.15(C)(1), Chapter 9 Table 8 and Section 240.4(D). Local code and equipment terminal ratings may require larger wire. Have a licensed electrician verify.

Common copper sizes under the NEC: 14 AWG for 15 A, 12 AWG for 20 A, 10 AWG for 30 A, 8 AWG for 40 A, and 6 AWG for 50–65 A. Enter your breaker size and this wire size calculator returns the smallest conductor that meets NEC Table 310.16, the small-conductor rule in 240.4(D), the 125% continuous-load rule, and — if you give a length — a 3% voltage-drop limit.

This is a planning tool, not professional advice. Your local inspector enforces the code edition your jurisdiction has adopted, and there may be local amendments. Have a licensed electrician design and install anything you aren't qualified to do.

How to use this calculator

  1. Choose a branch circuit/feeder/subpanel or a whole-dwelling service.
  2. Enter the breaker or load current in amps.
  3. Pick copper or aluminum and the temperature rating you can use: 60 °C for NM-B or UF cable, 75 °C for THWN/XHHW with 75 °C terminals, 90 °C for THHN when you need to derate.
  4. Say whether the load is continuous — expected to run at full current for 3 hours or more.
  5. Add the one-way length, voltage and phase for a voltage-drop check, plus ambient temperature and the number of current-carrying wires if above 30 °C or more than three.
  6. Read the minimum wire size, its derated ampacity and the voltage drop.

How it's calculated

  1. Required ampacity. For a continuous load, the conductor must carry the noncontinuous load plus 125% of the continuous load (NEC 210.19(A) for branch circuits). A continuous load is one whose maximum current is expected to continue for 3 hours or more. For a qualifying dwelling service, 310.12(A) instead allows 83% of the service rating.
  2. Table ampacity. Each size's allowable amps come from NEC 2023 Table 310.16 for the chosen metal and temperature column.
  3. Derating. That value is multiplied by the ambient correction factor from Table 310.15(B)(1)(1) and the bundling adjustment from Table 310.15(C)(1).
  4. Small-conductor cap. 14, 12 and 10 AWG are then capped by 240.4(D).
  5. Voltage drop. Drop % = k × L × I × R ÷ 1000 ÷ V × 100, where k is 2 for single-phase or √3 for three-phase, L is the one-way length in feet, I the current, R the resistance in ohms per 1,000 ft from Chapter 9 Table 8, and V the system voltage.
  6. The result is the smallest size that passes every check.

Worked examples

30 A circuit, 120 V, 50 ft, NM-B copper

10 AWG meets the ampacity rule, but its voltage drop at 50 ft is 3.03% — just over 3%. The calculator steps up to 8 AWG. At 150 ft, 8 AWG drops 5.8%, so you would need 4 AWG (3.7% on 6 AWG, still too high).

32 A continuous load, 240 V, copper at 75 °C

32 × 1.25 = 40 A required. 10 AWG (35 A at 75 °C) is too small, so the answer is 8 AWG (50 A).

30 A, THHN in a hot conduit with 6 current-carrying wires

At 45 °C ambient, 10 AWG THHN starts at 40 A (90 °C column), × 0.87 for heat × 0.80 for six conductors = 27.84 A — below 30 A. The calculator picks 8 AWG.

200 A dwelling service, aluminum

200 × 0.83 = 166 A at 75 °C, which needs 4/0 AWG aluminum (180 A) or 2/0 AWG copper.

Common answers

BreakerCopper (NM-B, 60 °C)Copper THHN (75 °C)Aluminum (75 °C)
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
100 A1 AWG3 AWG1 AWG
125 A1/0 AWG1 AWG2/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG250 kcmil

Wire ampacity chart (NEC 2023 Table 310.16)

Allowable amps for up to three current-carrying conductors in a raceway, cable or earth at 30 °C (86 °F) ambient.

SizeCu 60 °CCu 75 °CCu 90 °CAl 60 °CAl 75 °CAl 90 °C
14 AWG152025———
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Table values for 14, 12 and 10 AWG are higher than the breaker you may actually use: 240.4(D) caps copper at 15 A, 20 A and 30 A respectively, and aluminum at 15 A (12 AWG) and 25 A (10 AWG).

Which temperature column should I use?

  • 60 °C — NM-B (Romex) and UF cable, and any circuit 100 A or less unless terminals are marked 75 °C.
  • 75 °C — most breakers and lugs today; THWN, XHHW, USE conductors.
  • 90 °C — THHN insulation; the 90 °C value is only for derating, the final size must still satisfy the terminal rating.

Wire size for service and subpanels

For a 120/240 V service or feeder rated 100–400 A that carries the entire load of a one-family dwelling (or of one dwelling unit in a two-family or multifamily building), NEC 310.12(A) lets you size conductors at 83% of the rating. It applies only when no ambient or bundling correction is needed:

ServiceCopperAluminum
100 A4 AWG2 AWG
125 A2 AWG1/0 AWG
150 A1 AWG2/0 AWG
175 A1/0 AWG3/0 AWG
200 A2/0 AWG4/0 AWG
225 A3/0 AWG250 kcmil
250 A4/0 AWG300 kcmil
300 A250 kcmil350 kcmil
350 A350 kcmil500 kcmil
400 A400 kcmil—

A subpanel feeder does not qualify for the 83% rule unless it carries the entire dwelling load — use the full breaker rating.

Derating for heat and bundling

Table ampacities assume 30 °C (86 °F) and no more than three current-carrying conductors together. Hot attics, rooftops and full conduits reduce what a wire can safely carry:

Current-carrying conductorsAdjustment
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Derating starts from the conductor's insulation rating (e.g. 90 °C for THHN), but the result can never exceed the terminal rating of the breaker or lug.

Voltage drop

An Informational Note to NEC 210.19 (advisory, not enforceable) suggests no more than 3% drop on a branch circuit and 5% total for feeder plus branch circuit. Single-phase drop is 2 × L × I × R / 1000, where L is one-way length in feet, I the load in amps and R the DC resistance per 1000 ft from NEC Chapter 9 Table 8 (copper or aluminum, at 75 °C).

Common mistakes

  • Using the 90 °C column for the final size. THHN is rated 90 °C, but breakers and lugs usually are not. 110.14(C) limits circuits of 100 A or less (or 14–1 AWG) to the 60 °C column unless the equipment is listed and identified for 75 °C.
  • Putting 14 AWG on a 20 A breaker. 240.4(D) caps 14 AWG copper at 15 A no matter what the table says.
  • Forgetting the 125% rule. A load that runs 3 hours or more needs 25% more ampacity than its running current.
  • Using the 83% service rule on a subpanel. It applies only to conductors that carry the entire load of a dwelling unit.
  • Sizing aluminum like copper. Aluminum carries less current per size, so it usually needs one or two sizes larger.

Frequently asked questions

What size wire for a 30 amp circuit?

10 AWG copper (or 8 AWG aluminum) for a standard 30 A breaker. Go up a size for long runs where voltage drop exceeds 3%.

What size wire for 40 amps?

8 AWG copper at 60 °C (NM-B cable), or 8 AWG THHN copper using the 75 °C column. Aluminum needs 6 AWG at 60 °C, or 8 AWG where the breaker and lugs are rated 75 °C.

What size wire for 50 amps?

6 AWG copper with NM-B cable, or 8 AWG copper THHN/THWN in conduit with 75 °C terminals. Aluminum: 4 AWG at 60 °C, or 6 AWG with 75 °C terminals.

How many amps can 12 gauge wire carry?

12 AWG copper is limited to a 20 A breaker by NEC 240.4(D), even though Table 310.16 lists 20 A (60 °C), 25 A (75 °C) and 30 A (90 °C).

What size wire for 100 amp service?

For a 120/240 V dwelling service, NEC 310.12 allows 4 AWG copper or 2 AWG aluminum (83 A at the 75 °C column). For a 100 A subpanel feeder, use Table 310.16: 3 AWG copper or 1 AWG aluminum at 75 °C.

What size wire for 125 amps?

For a 125 A feeder or subpanel at 75 °C: 1 AWG copper or 2/0 AWG aluminum. If it is the service for the whole dwelling, the 83% rule in 310.12 allows 2 AWG copper or 1/0 AWG aluminum.

What size wire for 150 amps?

For a 150 A feeder at 75 °C: 1/0 AWG copper or 3/0 AWG aluminum. For a 150 A dwelling service under 310.12: 1 AWG copper or 2/0 AWG aluminum.

How many amps can 8 gauge wire carry?

8 AWG copper is rated 40 A at 60 °C, 50 A at 75 °C and 55 A at 90 °C in NEC Table 310.16. Most 8 AWG circuits are protected at 40 A (NM-B) or 50 A (THHN/THWN with 75 °C terminals).

What is the ampacity of 6 AWG wire?

6 AWG copper: 55 A (60 °C), 65 A (75 °C), 75 A (90 °C). 6 AWG aluminum: 40 / 50 / 55 A at 60/75/90 °C.

How many amps can 14 gauge wire carry?

14 AWG copper is limited to a 15 A breaker by NEC 240.4(D), even though Table 310.16 lists 15, 20 and 25 A in the 60, 75 and 90 °C columns.

What gauge wire for 20 amps?

12 AWG copper. 14 AWG is capped at 15 A by 240.4(D), so it can never be used on a 20 A breaker. Aluminum needs 10 AWG for 20 A.

What is the ampacity of 18 AWG wire?

18 AWG is not in Table 310.16 and is not used for household branch circuits. Where the NEC allows it, 240.4(D) limits 18 AWG copper to 7 A (continuous load no more than 5.6 A) and 16 AWG copper to 10 A (continuous load no more than 8 A), and only with breakers or fuses listed and marked for that wire size, or Class CC, CF, J or T fuses.

Sources & method

Results are estimates for general information. Found an error? It helps everyone — see our methodology.

Related calculators